Expansion Module 3 Analog Input 4 Pt100 2 Analog Output
Expansions Modules HV-E3AI4PT1002AO
3 channels of 14 bits precision current input, 4 channels of PT100 temperature input and 2 channels 10 bits precision voltage output.
3 channels of current,0~20mA and 4~20mA are optional; 2 channels of voltage, 0~5V and 0~10V are optional. They can be set by host machine.
Platinum resistance input, PT100.
3 channels A/D and 4 channels PT input with PID adjust function.
Can be set as special function module for HV series PLC, up to 7 modules can be connected.
PRODUCTS STANDARS
1. General Specifications.
Item | Analog current input(AD) | Temperature input (PT) | Analog voltage output(DA) |
Analog input | DC0~20mA、4~20mA | PT100 | - |
Range of temperature detect | - | -100~350℃ | - |
Max output range | DC0~40mA | - | - |
Range of analog output | - | - | DC0~5V、0~10V (External load resistance 2KΩ~1MΩ) |
Range of digital input | - | - | 10 bits(0~1023) |
Range of digital output | 14 bits(0~16383) | -1000~3500 | - |
Resolution | 1/16383(14Bit); Converted data are stored in PLC(14Bit) in hex form | 0.1℃ | 1/1023(10Bit); Converted data are stored in PLC in hex form(10Bit) |
PID output value | 0~K4095 | - | |
Integrated accuracy | 0.8% | ±0.5℃ | 0.8% |
Convert speed | 20ms/1 channel | 3ms/1 channel | |
Power for analog | DC24V±10%,100mA | ||
Installation | Fixed with M3 strews or directly installed in DIN46277(35mm width) guide rail | ||
External dimension | 63mm×102mm×73.3mm |